  • UHV-75kVA/75kV Series Resonance Solution

    The device has the protection functions of overvoltage, overcurrent, zero start, system mismatch (flashover) and so on.The whole device is lightweight and easy to use in the field.DSP platform technology is adopted.

    Product Details of UHV-75kVA/75kV Series Resonance Solution

    004-

    Product parameters:

    Suitable for handover and preventive testing of high-capacity, high-voltage capacitive specimens.

    DSC09400-



    Meet the test range:

    1. AC withstand voltage test for 1.5km 10kV/300mm2 cable, capacitance ≤ 0.5632 μ F, test frequency 30-300Hz, test voltage 22kV, test time 5min.

    2. AC withstand voltage test for 35kV/300mm2 cable at 0.35km, capacitance ≤ 0.0681 μ F, test frequency 30-300Hz, test voltage 52kV, test time 60min.

    3. AC withstand voltage test of 35kV main transformer, capacitance ≤ 0.02 μ F, test frequency 45-65Hz, test voltage not exceeding 68kV, test time 1min.

    4. AC withstand voltage test for electrical equipment such as 10kV switches, with a test frequency of 30-300Hz, a test voltage not exceeding 42kV, and a test time of 1 minute.


    Main components of the device:

    Serial number

    שם התקן

    Specification and model

    יחידה

    Quantity

    1

    Variable frequency power supply

    UHV-4kW

    Tower

    1

    2

    שנאי עירור

    UHV-4kVA/1.5/3/6kV/0.4kV

    Tower

    1

    3

    High voltage reactor

    UHV-25kVA/25kV

    Section

    3

    4

    Capacitive voltage divider

    UHV-1000pF/80kV

    מַעֲרֶכֶת

    1


    Main technical parameters and functions:

    קיבולת מדורגת

    75kVA

    מתח מדורג

    25k;75kV

    זרם מדורג

    3A;1A

    דיוק מדידה

    System RMS level 1.5

    Operating frequency

    30-300Hz

    Device output waveform

    Sinusoidal wave

    גורם איכות

    Device Q≥30(f=45Hz)

    קצב עיוות צורת גל

    Output voltage waveform distortion ≤1%

    ספק כוח קלט

    Single-phase 220 or three-phase 380V voltage, frequency 50Hz

    Working hours

    Allow continuous 60min under rated load; Overpressure 1.1 times 1 minute

    עליה בטמפרטורות

    Temperature rise ≤65K after continuous operation under rated load for 60 minutes

    Protection function

    Overvoltage, overcurrent, zero start, system mismatch (flashover) and other protection functions

    טמפרטורת הסביבה

    -20℃-55℃

    לחות יחסית

    ≤90%RH

    גוֹבַה

    ≤3000m