Product Introduction
Widely used in the installation and maintenance of various large transformer equipment, wind power generation, thermal power generation, power supply bureaus, etc., for oil purification and vacuum hot oil circulation drying. For the purification of insulating oil in transformers of 35KV-110KV-220KV, vacuum drying can be performed simultaneously with filtration. The dual-stage vacuum oil filter requires a dehydration and degassing system to quickly remove moisture, gases, and harmful components such as light hydrocarbons from the oil. It features a precision filtration system with multi-stage, progressively more refined filtration to effectively remove mechanical impurities from the oil; an electric heating constant temperature automatic control system ensures rapid oil heating and eliminates "dead oil zones." It guarantees uniform oil heating and stable oil temperature; it also has vacuum pumping and vacuum oil injection functions, and can perform ultimate vacuum extraction for transformers and GIS electrical equipment. Therefore, it meets various on-site requirements.
Working principle and process
After the treated oil passes through the magnetic filter, it enters the thick filter heater for heating. The heated oil passes through the second-stage filter from the oil suction pump to the spiral spray atomization system. The insulated oil becomes coarse-grained fog and falls on the reaction tower and enters the vacuum separation chamber. The moisture begins to evaporate. The oil mist, a multi-dimensional evaporation structure formed in the tank can achieve the purpose of purification through a short cycle. Oil products that have been removed from impurities, dehydrated, degasified and acid are completed through a precision filter under the action of the oil exhaust pump. The water vapor hot air separated from the vacuum separation chamber enters the inspector. Most of the water vapor condenses into the water tank. Outside the discharge machine, the hot air in the oil is discharged by a vacuum pump after cooling.
![]() |
פרמטרים טכניים
| Item | יחידה | Spec |
| דֶגֶם | SY/ZD-RM-150 | |
| Volume of flow | L/min | 150 |
| L/H | 8000-10000(Variable frequency adjustable) | |
| טווח בקרת טמפרטורה | ℃ | 0~100 |
| טמפרטורת עבודה | ℃ | 20~60 |
| Extreme vacuum | נו | ≤20 |
| Working vacuum degree | Mpa | -0.06~-0.099 |
| Gas content in oil | % | ≤0.1 |
| Work pressure | Mpa | ≤0.5 |
| Filtration accuracy | µm | ≤1 |
| Water content in oil | ppm | ≤3 |
| Oil breakdown voltage | KV | ≥65 |
| Heating power | KW | 72 |
| כוח מוחלט | KW | 80 |
| ספק כוח | Three-phase five-wire system 380V 50HZ | |
| Inlet/outlet pipe diameter | מ"מ | 50 |
| Continuous working hours | ח | ≥800 |
| Trouble-free working hours | ח | ≥8600 |
Oil quality indicators after insulating oil treatment
| Performance project | יחידה | Post-processing indicators | Test method |
| 1. Moisture content | % | none | GB/T511 |
| 2. Moisture content | PPM | ≤3 | GB/T7600 |
| 3. Pressure resistance value | KV | ≥65KV | GB, DL or IEC standards |
| 4. Residual gas | ≤1% | ≤0.5 | Gas content measurement methods shall be in accordance with relevant GB, DL or IEC standards. |
| 5. Acid value | 1µm | ||
| ![]() |
Product features
1. The combination of high vacuum, high pumping speed, internationally leading annular three-dimensional compound flash evaporation technology and microgram technology can efficiently and quickly remove harmful components such as water, dissolved micro water, free carbon, and gases.
2. Adopting a combination of multi-layer polymer mesh filtration and strong magnetic electrostatic adsorption for impurity removal technology, the filtration area is large, the pollutant holding capacity is strong, and the filtration accuracy is high, with ß 3 ≥ 1000
3. The compound three in one protection device can automatically protect high and low oil levels, automatically detect infrared bubbles, automatically control liquid levels, automatically maintain temperature, and automatically protect pressure. It has a high degree of automation and is sensitive and reliable to operate.
4. Specially suitable for vacuum oil injection, large-scale vacuum pumping, and vacuum drying of transmission and transformation equipment above 110KV during installation or maintenance sites.
5. Online oil filtration, can be unmanned, and the operating status is displayed by indicator lights.
6. Humanized design, low noise, simple operation, long maintenance intervals, low energy consumption, and cost savings in operation.
Function of Two-Stage Vacuum Oil Filter
The whole machine process mechanism and vacuum oil filter should have the functions of high-efficiency dehydration, degassing, filtration and drying transformer oil. The main components are: oil inlet pump, coarse filter, oil exhaust pump, degassing tank, heater, polymer purifier, magnetic filter, vacuum pumping system, constant temperature control and automatic oil temperature control system, electrical control cabinet, etc. The quality of the steel frame and other equipment should be intact and non-destructive, and the connection should not be loose. There are no welding tumors, burrs or rust spots at the welding part. The surface of the product adopts a plastic spraying process, and the surface should be smooth and bright. The machine should have the functions of filtration, purification and regeneration, which can efficiently remove moisture, gas and mechanical impurities in the insulating oil.